A Surge Protective Device (abbreviated as SPD) is suitable for AC 50/60Hz, 380V and below TN-S, TN-C-S, TT, IT and other power supply systems. It can be used as an equipotential connection at the interface of LPZ1, LPZ2 and LPZ3 zones. Its design complies with IEC61643-1, GB18802.1, and the shell is designed to be installed on a 35mm electrical rail. This product has a built-in failure disconnection device. When the surge protector fails due to overcurrent or overheating, the failure disconnection device can automatically disconnect it from the power grid. At the same time, the visual alarm indicator shows green (normal) and red (fault). The module can be replaced under working voltage conditions.